Who We Are
We offer TIC services to enhance fire, life, and electrical safety globally, confirming compliance and reducing risks.
by Joan Leedy, Technical Director
Dyne Fire Protection Labs offers testing of foam solutions to determine the concentration of the foam concentrate in the system water. Customers use this service by running a foam system in the field, collecting a sample of the discharge, and sending it to Dyne along with a sample of the foam concentrate and the system water. Using the foam concentrate and system water, Dyne technicians make up known foam solutions and then compare the refractive index of the known solutions to the solution provided by the customer. By using a bench-top analytical refractometer capable of reading refractive indexes accurately to the 5th decimal point, Dyne can provide an accurate result.
Unfortunately, we see many foam solutions that are not in specification. NFPA 11 requires a system proportion the foam “within minus 0 percent to plus 30 percent for the manufacturer’s listed concentrations, or plus 1 percentage point, whatever is less.” In order to pass this specification, a 3% foam system would need to proportion foam between 3.0% and 3.9%. Though a small number of foam concentrate samples fail in our laboratory, a larger amount of foam solutions fail. Let’s take a look at the reasons why a foam solution sample would fail when the proportioner is actually working as designed.
As you can see, there are a lot of things that could cause the concentration to be out of specification even though the system is performing as designed and all of them need to be considered when testing a foam proportioning system. Of course, an additional reason for an out of specification result, is that the proportioner is broken, plugged or that the wrong orifice has been installed.
Note: Many states are restricting the testing of systems that contain foams with fluorinated surfactants (PFAS), so this will eliminate the testing described in this paper. If these restrictions are imposed, verification of the proportioning will be done by using an alternative method, such as the surrogate liquid method or the water equivalency method.
If you have any questions regarding this article, please contact Dyne Fire Protection Labs at dyne.lab@nfpaglobal.com or (800) 632-2304.
©Dyne Fire Protection Labs 2021