In 2009, fire protection professionals changed their views of antifreeze sprinkler systems. That was the year that a woman was killed, and four others were injured when a kitchen grease fire caused a sprinkler system, containing antifreeze solution, to discharge. The antifreeze solution in the system was determined to be 71.2% glycerin and water. It ignited when discharged causing a deadly explosion. Prior to this incident, it was common practice to mix antifreeze solution in the field to charge a system.
Because of this event, several changes were made to the NFPA codes including the following:
NFPA 25, Inspection, Testing and Maintenance of Water-Based System, Section 5.3.4 requires annual testing of the antifreeze in the system. The specific gravity or refractive index shall be measured to determine the concentration of the antifreeze solution. If the concentration is outside the allowable range, the solution must be drained and replaced with a listed solution.
Dyne offers laboratory testing of antifreeze in sprinkler systems and the laboratory testing goes above and beyond the testing that can be conducted in the field. Dyne can:
Though laboratory testing is not a requirement of NFPA codes for Antifreeze Systems (field testing is acceptable), it may give you peace of mind to not rely on the paperwork and documentation for what type of solution is in the system by giving you absolute confirmation.