
When to Test or Replace Fire Sprinkler Systems
NFPA Global Solutions Guidance on NFPA 25 Requirements for Fire Sprinkler Systems Testing and Replacement
NFPA research unequivocally confirms that properly functioning sprinklers can significantly reduce the extent of property damage and increase the chance of building occupants escaping a fire. Whether you are an authority having jurisdiction (AHJ), an inspection, testing, and maintenance (ITM) contractor, facility manager, or building owner, it is critical you understand NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems requirements, and the latest guidance for sprinkler replacement and testing intervals.
To simplify the complexities, the following covers rules for field sprinkler sampling, when and why sprinklers need to be replaced or tested, at what intervals, and additional considerations and recommendations from NFPA Global Solutions. Use our handy workflow exercise at the end to confirm when your system is due for testing or replacement.
What is NFPA 25, and What Does it Say About Testing and Replacing Fire Sprinklers?
NFPA 25 is the benchmark resource for water-based fire protection systems inspection, testing, and maintenance. The standard provides expert-developed content to help ensure automatic extinguishing systems (AES) are ready to respond in an emergency.
According to NFPA 25:
- You must periodically replace sprinklers or test a minimum of 4 sprinklers or 1% of the sprinklers in a sample area
- Sample area is defined by the building owner and/or their designated representative and can be as big or as small as desired
- Treat different environments as different sample areas (i.e. living quarters, offices, parking garage, swimming pool)
- A representative sample will contain at least one of each type of sprinkler and at least one sprinkler from each type of environment
- Samples should be taken at random
- If even one sprinkler fails in a sample set, all samples in the area represented by that sample set need to be replaced
Why are Sprinklers Replaced and Tested on Different Intervals?
When to test or replace sprinklers depends on a variety of considerations such as the response type, age, and environment of the equipment. For instance, degradation can be greatly accelerated in sprinklers used in a harsh environment, making replacement/testing due much sooner. Over the years and the last several editions of NFPA 25, many replacement and initial fire sprinkler testing intervals have been extended due to factors such as:
- Low failure rates in newer technologies such as fast-response sprinkler systems
- Dwindling use of the O-ring water seal design in dry sprinklers—a design not been listed by Underwriters Laboratories (UL) in over 20 years—resulting in a significant drop in failure rates
- Use of corrosion-resistant material, coatings, or plating on sprinklers for improved protection from degradation in harsh environments
How Do I Know When Fire Sprinklers Need to be Tested or Replaced?
While fire sprinkler testing and replacement intervals can vary widely and depend on a range of circumstances, the 2023 edition of NFPA 25, section 5.3.1, provides definitive guidance. Reference the following requirements for field sprinkler testing intervals years after system installation:
- Sprinklers in Harsh Environments that ARE NOT listed as corrosion resistant (Test or replace 5 years after installation)
- Sprinkler in Harsh Environments that ARE listed as corrosion resistant (Test or replace 10 years after installation)
- Early Suppression Fast-Response (ESFR), Mode Specific Application (CMSA), and Dry Sprinklers (Test or replace 20 years after installation)
- Fast-Response Sprinklers (Test or replace 25 years after installation)
- All Other Sprinklers (Test or replace 50 years after installation)
What Are the Testing Intervals of Tested Sprinklers That Remain in Service?
Should the sprinklers in the sample area be initially tested instead of replaced, and if the testing finds the sprinklers to be still acceptable (i.e., those sprinklers represented by the sample set tested remain in service), testing would then be needed periodically thereafter.
The following are the rules for subsequent fire sprinkler testing intervals according to NFPA 25:
- If sprinklers are 75 years old or older (Replace or test again in 5 years)
- If newer than 75-year-old sprinklers ARE installed in a harsh environment (Replace or test again in 5 years)
- If newer than 75-year-old sprinklers ARE NOT installed in a harsh environment (Replace or test again in 10 years)
Should Fire Sprinklers Featuring O-Ring Water Seals Be Replaced?
NFPA Global Solutions recommends identifying any sprinklers that may feature an O-ring water seal design. While not part of NFPA 25 requirements, this design has a notoriously high failure rate (>50%) and was the subject of several recalls. In other words, the chances of one or more sprinklers in a sample set of four or more failing is high. Remember that NFPA 25 requires the replacement of all sprinklers represented by that sample set to be replaced if even just one fails. As a result, outright replacement of O-ring designs is recommended.
Is My Fire Sprinkler System Due for Testing or Replacement?
Now that you’ve read the latest information and guidance and understand how and when to test, use the workflow below to see if your system needs replacement or testing.
References: Mode Specific Application (CMSA) Sprinkler - A type of spray sprinkler that is capable of producing characteristic large water droplets and that is listed for its capability to provide fire control of specific high-challenge fire hazards. Corrosion-Resistant Sprinkler - A Sprinkler fabricated with corrosion-resistant material, or with special coatings or platings, to be used in an atmosphere that would normally corrode sprinklers. Dry Sprinkler - A sprinkler secured in an extension nipple that has a seal at the inlet end to prevent water from entering the nipple until the sprinkler operates. Early Suppression Fast-Response (ESFR) Sprinkler - A type of fast-response sprinkler that has a thermal element with an RTI of 50 (meter-seconds)1/2 or less and is listed for its capability to provide fire suppression of specific high-challenge fire hazards. Examples of Harsh Environments: Paper mills, packing houses, tanneries, alkali plants, organic fertilizer plants, foundries, forge shops, fumigation areas, pickle and vinegar works, stables, storage battery rooms, electroplating rooms, galvanizing rooms, steam rooms of all descriptions including moist vapor dry kilns, salt storage rooms, locomotive sheds or houses, driveways, areas exposed to outside weather, areas around bleaching equipment in flour mills, and portions of any area where corrosive vapors prevail.
Final Thoughts on Replacing and Testing Fire Sprinklers
Having a clearer understanding of the requirements and intervals for initial and subsequent replacement and testing of sprinklers can help mitigate risks and keep your people and facility safer. Be sure to reference the information in this post and NFPA 25 in your work, and feel free to reach out to NFPA Global Solutions for additional support. We offer advisory services, digital products, and compliance solutions, including fast and unbiased testing of fire sprinklers and other fire suppression equipment and systems.